FRTU(Pole-Mounted)
Installed on 22.9kV V-Y overhead distribution lines. Reduces fault detection time by monitoring distribution line data in real time, minimizes outage area and duration by isolating the faulted section and restoring healthy sections by remote control, and improves power quality through distribution line information management.
A dedicated catalogue for this model is in preparation. The general catalogue covers the product.
Main functions
- Used on overhead distribution lines
- Installation: gas-insulated switch (SF6)
- Obtaining distribution line data (current/voltage, power factor, active/reactive/apparent power)
- Detection of a distribution line fault (instantaneous/permanent fault)
- Embedded Fault Indicator
- Monitoring status of the switchgear and control box
- Remote control (open, close)
- Data communication with the remote operating system using DNP protocol
- Local and remote setting
- Monitor with self-diagnosis function
- Manage line event
Specifications
Specification
| Division | Item | Specification |
|---|---|---|
| Rated | Rated frequency | 60Hz |
| Rated voltage(PT) | 1V ~ 6V(±3%) | |
| Over Voltage : 25% ~ 150% Continuous | ||
| Rated current(CT) | 0.003 ~ 0.400A(±1A or ±3%) | |
| 0.401 ~ 10.000A(±3%) | ||
| Over Current : 0 ~ 400% Continuous, 400% ~ 2500% 1s | ||
| Communication | Communication port | DNP 3.0 Protocol, Two-line/four-line type, RS232C, 1200~38400bps, D-SUB 9pin |
| CONSOLE PORT(for maintenance purposes) | PC S/W, RS232C, 115200bps, D-SUB 9pin, Male | |
| Usage temperature Maximum 70℃~ Minimum -30℃ | ||
| Elevation 1,000m Less than | ||
| Power | Input power | DC 24V (21~29V) |
| Power consumption | 15W Less than | |
| Enclosure | Form | Mounting type |
| Weight | 4.8kg | |
| Material | Aluminum | |
| Display Unit | LCD, 4Line, 20 Character |