Fault Recorder Panel

Fault Recorder Panel

In power plants or substations, a variety of events may occur, including the following: device operation or control for electrical power facilities and the operation of circuit breakers by protection devices in case of failure in power plants or substations. Accurate analysis for those various events plays a crucial role not only in stable and reliable operation of the power system facilities but also in measures to prevent potential accidents in the future. Fault recorder panel provides a function to record, store and analyze a wide range of power system data.

SPR-K010

Main functions

Triggering by power swing detection; manual or automatic triggering

Specification

DivisionItemSpecification
RatedInput powerDC 90~140[V],60Hz
Rated voltage(PT)115/√3[V]
Rated current(CT)5[A]
Digital output10[A] : 250VAC 8 points
Digital inputDC 70 ~ 150[V] 96 points
CommunicationCommunication portRS-232, Ethernet, Fiber Optic
ProtocolIEC61850, IEEE C37.118, TCP/IP
Display 10.4 inch Color TFT-LCD(1024×768)